GV7RS80
Giá: Liên hệ
Mã sản phẩm: GV7RS80
| range |
TeSys
|
|
|---|---|---|
| product name |
TeSys GV7
|
|
| device short name |
GV7R
|
|
| device application |
Motor
|
|
| poles description |
3P
|
|
| network type |
AC
|
|
| utilisation category |
AC-3 conforming to IEC 60947-4-1
|
|
| network frequency |
50/60 Hz conforming to IEC 60947-4-1
|
|
| breaking capacity |
50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
| [Ics] rated service short-circuit breaking capacity |
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
| thermal protection adjustment range |
48…80 A
|
|
| trip unit technology |
Thermal-magnetic
|
| mounting mode |
By screws
By clips |
|
|---|---|---|
| mounting support |
Kit for fixing the switchgear
Rail Flush Panel mounting |
|
| mounting position |
Vertical
|
|
| motor power kW |
37 kW at 400...415 V AC 50/60 Hz
45 kW at 500 V AC 50/60 Hz 55 kW at 500 V AC 50/60 Hz 55 kW at 660...690 V AC 50/60 Hz |
|
| control type |
Rocker lever
|
|
| [Ue] rated operational voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
| [Ui] rated insulation voltage |
750 V AC 50/60 Hz conforming to IEC 60947-2
|
|
| [Ith] conventional free air thermal current |
80 A conforming to IEC 60947-4-1
|
|
| [Uimp] rated impulse withstand voltage |
8 kV IEC 60947-2
|
|
| power dissipation per pole |
5 W
|
|
| power dissipation per pole |
5 W
|
|
| mechanical durability |
50000 cycles
|
|
| electrical durability |
30000 cycles for AC-3 at 440 V In
50000 cycles for AC-3 at 440 V In/2 |
|
| maximum operating rate |
25 cyc/h
|
|
| rated duty |
Continuous conforming to IEC 60947-4-1
|
|
| connection pitch |
35 mm without spreaders
45 mm with spreaders |
|
| connections - terminals |
Bars
Cable with lug - external diameter: 10 mm Screw Bare cable connectors 1.5…95 mm² |
|
| tightening torque |
10 N.m on screw M6 screw type
15 N.m on bare cable connectors for cable 1.5…95 mm² |
|
| mechanical robustness |
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations: 2.5 Gn, 0...25 Hz conforming to IEC 60068-2-6 |
|
| suitability for isolation |
Yes conforming to IEC 60947-1
|
|
| phase failure sensitivity |
Yes conforming to IEC 60947-4-1 § 7-2-1-5-2
|
|
| height |
161 mm
|
|
| width |
105 mm
|
|
| depth |
111 mm
|
|
| net weight |
2.04 kg
|
| standards |
EN/IEC 60947-1
EN/IEC 60947-4-1 EN/IEC 60947-2 NF C 79-130 NF C 63-120 VDE 0660 VDE 0113 NF C 63-650 |
|
|---|---|---|
| product certifications |
UL
DNV |
|
| protective treatment |
TC
|
|
| IP degree of protection |
IP405 conforming to IEC 60529 (with terminal shrouds)
|
|
| pollution degree |
3
|
|
| ambient air temperature for operation |
-25…70 °C
|
|
| ambient air temperature for storage |
-55…95 °C
|
|
| fire resistance |
960 °C conforming to IEC 60695-2-1
|
|
| operating altitude |
2000 m
|
| EU RoHS Directive |
Not applicable, out of EU RoHS legal scope
|
|
|---|---|---|
| Environmental Disclosure |
| Warranty |
18 months
|
|---|



















