ACB MVS40H3MF6L

ACB MVS40H3MF6L
ACB MVS40H3MF6L

Giá: Liên hệ

Mã sản phẩm: MVS40H3MF6L

Main
range of product
EasyPact MVS
 
range
EasyPact
 
product name
MVS40H
 
device short name
MVS40H
 
product or component type
Circuit breaker
 
device application
Distribution
 
poles description
3P
 
protected poles description
3P 3d
 
network type
AC
 
breaking capacity code
H
 
suitability for isolation
Yes conforming to IEC 60947-2
 
utilisation category
Category B
 
trip unit name
ET6G
 
trip unit technology
Electronic
 
trip unit rating
4000 A
 
Complementary
network frequency
50/60 Hz
 
control type
Manually operated
 
mounting mode
Fixed
 
mounting support
Rail
Base plate
 
connection position
Horizontal
Vertical
 
location of connection
Rear
 
[In] rated current
4000 A at 40 °C
 
[Ui] rated insulation voltage
1000 V AC 50/60 Hz conforming to IEC 60947-2
 
[Uimp] rated impulse withstand voltage
12 kV conforming to IEC 60947-2
 
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
 
circuit breaker CT rating
4000 A
 
breaking capacity
65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
 
[Ics] rated service breaking capacity
65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
 
mechanical durability
20000 cycles (with maintenance) conforming to IEC 60947-2
10000 cycles (without maintenance) conforming to IEC 60947-2
 
electrical durability
Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
 
connection pitch
115 mm without spreader
 
contact position indicator
Yes
 
[Icm] rated short-circuit making capacity
143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
 
[Icw] rated short-time withstand current
65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
 
trip unit protection functions
LSIG
 
protection type
Earth fault
Instantaneous short-circuit protection
Short time short-circuit protection
Overload protection (long time)
 
fault indication
Overload
Short-circuit
Internal fault
Earth fault
 
long time pick-up adjustment type Ir
Adjustable 9 settings
 
long time pick-up adjustment range
0.4...1 x In
 
long time delay adjustment type
Adjustable 9 settings
 
[tr] long-time delay adjustment range
0.5…24 s at 6 x Ir
 
short-time pick-up adjustment type Isd
Adjustable 9 settings
 
[Isd] short-time pick-up adjustment range
1.5...10 x Ir
 
short-time delay adjustment type
Adjustable 5 settings
 
[tsd] short-time delay adjustment range
100…400 ms
 
instantaneous pick-up adjustment type Ii
Adjustable 9 settings
 
instantaneous pick-up adjustment range
Off
2...15 x In
 
ground-fault pick-up adjustment type
Adjustable 9 settings
 
ground-fault time delay adjustment type -tg
Adjustable 5 settings
 
[tg] ground-fault time delay adjustment range
100…400 ms
 
[Ig] ground-fault pick-up adjustment range
500...1200 A
 
zone selective interlocking ZSI
With
 
current sensor rating range
1000/4000 A
 
maximum breaking time
25 ms
 
maximum closing response time
70 ms
 
height
352 mm
 
width
422 mm
 
depth
297 mm
 
net weight
60 kg
 
Environment
standards
IEC 60947-2
 
product certifications
GOST
CCS
CCC
IEC
 
IP degree of protection
IP40
 
pollution degree
4 conforming to IEC 60664-1
 
ambient air temperature for operation
-5…70 °C
 
ambient air temperature for storage
-40…85 °C without control unit
-25…85 °C with control unit
 
Offer Sustainability
EU RoHS Directive  
Mercury free
Yes
 
RoHS exemption information  
China RoHS Regulation
China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
 
Environmental Disclosure  
Circularity Profile  
Contractual warranty
Warranty
18 months

Sản phẩm khác