ATS48M12Q

ATS48M12Q
ATS48M12Q

Giá: Liên hệ

Mã sản phẩm: ATS48M12Q

main
range of product
Altistart 48
 
product or component type
Soft starter
 
product destination
Asynchronous motors
 
product specific application
Heavy duty industry and pumps
 
device short name
ATS48
 
power supply voltage
230...415 V - 15...10 %
 
motor power kW
630 kW at 400 V connection in the motor supply line for standard applications
710 kW at 400 V connection to the motor delta terminals for severe applications
250 kW at 230 V connection in the motor supply line for severe applications
355 kW at 230 V connection in the motor supply line for standard applications
500 kW at 230 V connection to the motor delta terminals for standard applications
500 kW at 400 V connection in the motor supply line for severe applications
 
power dissipation in W
2865 W for severe applications
3497 W for standard applications
 
utilisation category
AC-53A
 
type of start
Start with torque control (current limited to 5 In)
 
Icl nominal current
1200 A for connection in the motor supply line for severe applications
1200 A for connection in the motor supply line for standard applications
2078 A for connection to the motor delta terminals for severe applications
2078 A for connection to the motor delta terminals for standard applications
 
IP degree of protection
IP00
 
Complementary
assembly style
With heat sink
 
function available
External bypass (optional)
 
power supply voltage limits
195…456 V
 
power supply frequency
50...60 Hz - 5...5 %
 
power supply frequency limits
47.5...63 Hz
 
device connection
In the motor supply line
To the motor delta terminals
 
factory setting current
1045 A
 
[Uc] control circuit voltage
220 - 15 % to 415 + 10 %, 50/60 Hz
 
control circuit consumption
80 W
 
discrete output number
2
 
discrete output type
(LO1) logic output 0 V common configurable
(LO2) logic output 0 V common configurable
(R1) relay outputs fault relay NO
(R2) relay outputs end of starting relay NO
(R3) relay outputs motor powered NO
 
output absolute accuracy precision
+/- 5 %
 
minimum switching current
10 mA at 6 V DC for relay outputs
 
maximum switching current
Logic output 0.2 A at 30 V DC
Relay outputs 1.8 A at 230 V AC inductive load, cos phi = 0.5 20 ms
Relay outputs 1.8 A at 30 V DC inductive load, cos phi = 0.5 20 ms
 
discrete input number
5
 
discrete input type
PTC, 750 Ohm at 25 °C
(Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
 
discrete input voltage
24 V <= 30 V
 
discrete input logic
Positive logic Stop, Run, LI3, LI4 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA
 
starting current
0.4...1.3 Icl adjustable
 
analogue output type
Current output AO: 0-20 mA or 4-20 mA, impedance <500 Ohm
 
communication port protocol
Modbus
 
connector type
1 RJ45
 
communication data link
Serial
 
physical interface
RS485 multidrop
 
transmission rate
4800, 9600 or 19200 bps
 
max nodes number
31
 
protection type
Phase failure: line
Thermal protection: motor
Thermal protection: starter
 
marking
CE
 
type of cooling
Forced convection
 
operating position
Vertical +/- 10 degree
 
height
890 mm
 
width
770 mm
 
depth
315 mm
 
net weight
115 kg
 
Motor power range AC-3
250…500 kW at 200…240 V 3 phases
560…900 kW at 380…440 V 3 phases
 
motor starter type
Soft starter
 
Environment
electromagnetic compatibility
Conducted and radiated emissions level A conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 61000-4-2
Immunity to electrical transients level 4 conforming to IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
Voltage/current impulse level 3 conforming to IEC 61000-4-5
 
standards
EN/IEC 60947-4-2
 
product certifications
UL
CSA
GOST
TCF
SEPRO
DNV
NOM 117
CCC
C-Tick
 
vibration resistance
1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-6
1.5 mm (f= 2…13 Hz) conforming to EN/IEC 60068-2-6
 
shock resistance
15 gn for 11 ms conforming to EN/IEC 60068-2-27
 
noise level
60 dB
 
pollution degree
Level 3 conforming to IEC 60664-1
 
relative humidity
0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
 
ambient air temperature for operation
40…60 °C (with current derating of 2 % per °C)
-10…40 °C (without)
 
ambient air temperature for storage
-25…70 °C
 
operating altitude
<= 1000 m without
> 1000...2000 m with current derating of 2.2 % per additional 100 m
 
Offer Sustainability
Sustainable offer status
Green Premium product
 
REACh Regulation  
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
 
Mercury free
Yes
 
RoHS exemption information  
China RoHS Regulation  
Environmental Disclosure  
Circularity Profile  
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
 
Contractual warranty
Warranty
18 months

Sản phẩm khác